This rule is frequently misunderstood or ignored, and many people have
drafting problems with their fireplaces for this reason. This rule is
fairly simple, however, and must be followed in every vented fireplace
installation.
National Fuel Gas Code, ANSI Z223.1, Section 10.5.2.1, states the rule: "A chimney for residential-type or low-heat gas utilization equipment shall extend at least 3 ft. (0.9 m) above the highest point where it passes through a roof of a building and at least 2 ft. (0.6 m) higher than any portion of a building within a horizontal distance of 10 ft. (3 m)."
The basic rule is this: the bottom of the vent termination must clear the roof penetration point (the upper edge) by at least 3 feet; further, the bottom of any fireplace vent termination must clear anything within a 10 foot radius by at least 2 feet. This includes: the peak of the house, parapet, dormer, chimney or spire.
The following diagrams illustrate this rule. |